High exhaust ventilation…

ERO number

019-4974

Comment ID

60116

Commenting on behalf of

Individual

Comment status

Comment approved More about comment statuses

Comment

High exhaust ventilation rates makes it difficult to achieve the required TEDI of TGS Tier 2/3/4 and Passive House Standard.

Please consider:

Adopting ASHRAE 62.2 Ventilation and Acceptable Indoor Air Quality in Residential Buildings under the OBC for all residential buildings, and removing the requirement for residential buildings to comply with ASHRAE 62.1 Ventilation for Acceptable Indoor Air Quality.

OR

Providing an Alternative Compliance Path for Ventilation Rates for multifamily Passive House or TGS Tier 2, 3, 4 buildings under the OBC, allowing these buildings to be designed to meet the continuous exhaust rates under ASHRAE 62.2 Table 5-2 (NOT ASHRAE 62.1) OR International Mechanical Code Table 403.3.2.3: