The proposed Clause 3.1.9.4(5) appears to contradict the requirements for fire-stopping of combustible penetrations contained in Clause 3.1.9.1 and 3.1.9.4(4) where combustible DWV is permitted on both sides of a (vertical) fire separation. Clause 3.1.9.1 mandates firestopping for penetrations and does not limit the combustible pipe to one side of a fire penetration. Clause 3.1.9.4(5) on its own is not required. The old wording of "each" would be preferred or better yet remove the sentence entirely per the 2015 OBC. This NBC wording has caused a lot of confusion over it’s interpretation over the years.