Comment
The proposed Clause 3.1.9.4(7) mandates that regardless of whether the penetrating item material is combustible or noncombustible pipe, the penetration would require a firestop with a 50Pa pressure differential. For combustible pipe penetrations, the 50Pa is ok but for noncombustible pipe penetrations, they should be fire-stopped in accordance with 3.1.9.1 with no 50Pa requirement.
The following revision would correct this item: “…exposed side when the penetrating item is combustible or in accordance with Clause 3.1.9.1 when the penetrating item is noncombustible.”
Submitted March 10, 2022 10:12 AM
Comment on
Proposed Changes for the Next Edition of Ontario’s Building Code (Winter Consultation)
ERO number
019-4974
Comment ID
59986