The proposed Clause 3.1.9.4…

ERO number

019-4974

Comment ID

59986

Commenting on behalf of

IPEX Management Inc.

Comment status

Comment approved More about comment statuses

Comment

The proposed Clause 3.1.9.4(7) mandates that regardless of whether the penetrating item material is combustible or noncombustible pipe, the penetration would require a firestop with a 50Pa pressure differential. For combustible pipe penetrations, the 50Pa is ok but for noncombustible pipe penetrations, they should be fire-stopped in accordance with 3.1.9.1 with no 50Pa requirement.

The following revision would correct this item: “…exposed side when the penetrating item is combustible or in accordance with Clause 3.1.9.1 when the penetrating item is noncombustible.”